Generator Waste Heat Recovery: Systems, Sizing and Payback
A diesel generator converts only about 35 to 45% of the fuel energy into electrical output; the rest is rejected as the heat in the exhaust gas, the jacket water, the lubricating oil, and the radiation. The waste heat recovery system captures part of that heat and uses it for the heating, the hot water, the absorption cooling, or the process steam, and it turns a generator set into a combined heat and power (CHP) plant that uses the fuel at an overall efficiency of 80 to 90%. This guide covers the heat sources and the recoverable energy, the exhaust and the jacket water systems, the heat exchanger types, the sizing and the temperatures, the applications, the integration and the controls, the economics and the payback, and the maintenance of the recovery equipment.
The waste heat recovery is attractive wherever there is a continuous electrical load and a continuous heat demand: the hospitals, the hotels, the industrial plants, the food processing, the greenhouses, and the district heating schemes. The heat is recovered from the exhaust gas, which is the highest-temperature source, and from the engine jacket water, which is the largest heat flow, and the recovered heat replaces the fuel that would otherwise be burned in a boiler. The recovered heat is a by-product of the electricity generation, and its cost is effectively the marginal cost of the fuel.
Heat Sources and Recoverable Energy
The energy balance of a typical diesel generator shows the distribution of the fuel energy:
| Energy Stream | Share of Fuel Energy | Temperature | Recoverable |
|---|---|---|---|
| Electrical output | 35-45% | — | Delivered |
| Exhaust gas | 25-35% | 350-550 °C | Yes, with the exhaust heat exchanger |
| Jacket water | 20-30% | 75-95 °C | Yes, with the plate or the shell exchanger |
| Lubricating oil | 3-5% | 80-95 °C | Yes, with the oil cooler exchanger |
| Radiation and other | 3-8% | — | Not practical |
The exhaust gas is the highest-quality heat: it leaves the engine at 350 to 550 °C, and the exhaust heat exchanger can recover a large part of that heat to produce hot water, steam, or thermal oil. The jacket water is the largest recoverable flow: the engine cooling system carries 20 to 30% of the fuel energy at 75 to 95 °C, and a heat exchanger transfers that heat to the heating circuit without disturbing the engine cooling.
The lubricating oil circuit adds a smaller heat flow, and the oil cooler exchanger can recover the oil heat where the demand is present. The total recoverable heat is typically 40 to 50% of the fuel energy, and the combined efficiency of the CHP plant reaches 80 to 90%. The radiator guide covers the conventional heat rejection, and the oil cooler guide covers the oil circuit heat.
The Exhaust Heat Recovery System
The exhaust heat recovery is performed by the exhaust heat exchanger, also called the waste heat boiler or the economiser. The hot exhaust gas passes through the tubes or the shell of the exchanger, and the water or the thermal oil on the other side absorbs the heat. The exchanger is installed in the exhaust pipe between the engine turbocharger outlet and the silencer, and it is sized for the exhaust flow and the required heat output.
The exhaust heat exchanger produces hot water up to about 120 °C at the atmospheric pressure, steam at a low pressure, or thermal oil at a higher temperature, and the output depends on the exchanger design and the operating pressure. The exhaust gas must not be cooled below the acid dew point, which is roughly 120 to 150 °C depending on the sulphur content of the fuel, because the condensation of the sulphuric acid corrodes the exchanger and the exhaust pipe. The exchanger is therefore controlled to maintain the minimum exhaust outlet temperature.
The exhaust system includes the bypass and the control dampers, the expansion joints, the silencer, and the stack, and the system is designed with the back pressure within the engine limit. The exchanger is drained and cleaned, and the soot and the ash are removed periodically. The exhaust manifold guide covers the exhaust system, and the turbocharger guide covers the exhaust-driven component.
The Jacket Water Heat Recovery System
The jacket water heat is recovered by the plate heat exchanger or the shell and tube exchanger installed in the engine cooling circuit. The engine coolant flows through the primary side, and the heating circuit water flows through the secondary side, and the heat is transferred without mixing the circuits. The engine coolant temperature is maintained by the thermostat at the normal operating temperature, and the heat exchanger is sized so that the engine cooling is not disturbed.
The jacket water system has two operating modes. In the normal mode, the engine coolant is cooled by the radiator and the heat is rejected; in the recovery mode, the heat exchanger takes the heat and the radiator is bypassed or trimmed. The system is controlled so that the engine coolant temperature stays in the correct range under all loads, and the cooling is restored if the heat demand falls.
The recovered jacket water is typically at 75 to 90 °C, which is suitable for the space heating, the domestic hot water, and the absorption cooling. The water quality of the secondary circuit is controlled, and the plate exchanger is cleaned at the interval. The water pump guide covers the circulation, and the thermostat guide covers the temperature control.
Heat Exchanger Types
The heat exchangers used in the waste heat recovery are selected by the duty, the temperature, and the pressure:
| Exchanger Type | Duty | Advantages | Typical Service |
|---|---|---|---|
| Plate heat exchanger | Jacket water to water | Compact, high efficiency, easy to clean | Heating and hot water |
| Shell and tube exchanger | High temperature and pressure | Robust, high pressure rating | Exhaust and steam duties |
| Fin tube exchanger | Exhaust gas to water or oil | High surface area, compact | Exhaust heat recovery |
| Exhaust gas boiler | Steam generation | Produces process steam | Industrial steam users |
The plate heat exchanger is the standard for the jacket water recovery: it is compact, has a high heat transfer coefficient, and is opened for the cleaning. The shell and tube exchanger is used for the exhaust duties and the higher pressures, and the fin tube exchanger maximises the heat transfer from the exhaust gas to the water or the thermal oil.
The exhaust gas boiler produces the low-pressure steam for the process use, and it is a larger installation with the steam drum, the level control, and the safety valves. The exchanger selection is based on the heat duty, the temperatures, the pressure, and the fouling, and the design is verified by the manufacturer. The installation guide covers the pipework, and the safety guide covers the pressure safety.
Sizing and Temperatures
The recovery system is sized from the recoverable heat and the heat demand. The recoverable heat is estimated from the engine fuel consumption and the heat balance: at the rated load, a generator with a 30% electrical efficiency rejects roughly 1.5 to 2.0 kW of recoverable heat per kW of electrical output, depending on the exhaust and the jacket water shares. The heat demand is the heating, the hot water, or the process load, and the recovery system is sized for the smaller of the two at the design conditions.
The temperature requirements set the exchanger design: the heating circuit needs the supply temperature of 60 to 90 °C, the domestic hot water needs 60 to 65 °C, the absorption chiller needs 75 to 95 °C, and the process steam needs 110 to 160 °C. The jacket water at 75 to 95 °C covers the first three, and the exhaust heat is used for the higher temperatures and the steam.
The recovered heat is stored or dumped when the heat demand is lower than the generation: the thermal storage tank accumulates the heat, and the radiator or the dump cooler rejects the surplus. The control system matches the heat generation to the demand, and the engine is not constrained by the heat demand unless the CHP operation is the priority. The compliance guide covers the CHP regulations, and the radiator guide covers the dump cooling.
Applications of the Recovered Heat
The recovered heat is used in the applications that need the low-temperature heat continuously:
- Space heating: the hot water at 60-90 °C for the radiators, the fan coils, and the underfloor systems.
- Domestic and process hot water: the preheat and the direct heating of the water for the hotels, the hospitals, and the industry.
- Absorption cooling: the heat drives the absorption chiller to produce the chilled water for the air conditioning.
- Process steam: the exhaust gas boiler produces the low-pressure steam for the sterilisation, the cooking, and the washing.
- Agricultural and horticultural heating: the greenhouses and the drying facilities use the recovered heat.
- District heating: the recovered heat is fed into the local heating network.
The selection of the application is based on the temperature requirement and the load profile: the continuous heat demand gives the best payback, and the seasonal demand gives a lower utilisation. The recovered heat replaces the boiler fuel, and the saving is the fuel cost that would have been spent. The sourcing guide covers the feasibility data, and the after-sales guide covers the support.
Integration and Controls
The recovery system is integrated with the engine and the heat users by the pipework, the pumps, the control valves, and the control system. The engine coolant circuit is protected by the thermostatic control, and the heat exchanger is protected against the over-temperature and the over-pressure. The exhaust system is protected by the bypass and the minimum temperature control, and the steam equipment is protected by the safety valves and the level controls.
The control system monitors the engine load, the coolant temperatures, the heat exchanger outlet temperatures, the heat demand, and the storage levels, and it modulates the flow to match the generation to the demand. The CHP control can be heat-led or electricity-led: in the heat-led mode, the engine follows the heat demand and the electricity is the by-product; in the electricity-led mode, the heat is stored or dumped when the demand is low.
The metering is part of the CHP plant: the electrical output, the heat output, the fuel input, and the efficiencies are measured and recorded, and the performance is verified against the design. The control and the metering are the basis of the incentive and the carbon reporting schemes. The compliance guide covers the reporting, and the ATS transfer switch guide covers the electrical integration.
Economics and Payback
The payback of the waste heat recovery is calculated from the capital cost, the recovered energy value, and the utilisation. The recovered heat is valued at the displaced boiler fuel cost, and the annual saving is the recovered energy multiplied by the utilisation and the fuel price. The capital cost includes the heat exchangers, the pipework, the pumps, the controls, the installation, and the engineering, and the payback period is the capital cost divided by the annual saving.
A typical installation with a continuous heat demand recovers the investment in 2 to 5 years, and the payback is shorter where the fuel is expensive, the utilisation is high, and the boiler efficiency is low. The recovered heat reduces the carbon footprint: the CHP plant uses less fuel for the same useful output, and the emissions are lower per unit of useful energy.
The feasibility study is the first step: the heat demand, the load profile, the recoverable heat, the capital cost, and the fuel price are analysed, and the CHP plant is designed for the optimum size. The study also covers the regulations, the grid connection, and the incentives. The sourcing guide explains the feasibility data, and the maintenance schedule guide covers the operating cost.
Maintenance of the Recovery Equipment
The recovery equipment is maintained on a schedule that follows the plant maintenance:
- Clean the exhaust heat exchanger and remove the soot and the ash at the interval.
- Check the plate heat exchanger for the fouling and the leakage, and clean the plates.
- Inspect the pipework, the pumps, the valves, and the insulation for the leaks and the damage.
- Test the control valves, the thermostats, the safety valves, and the level controls.
- Check the water quality of the heating circuit and the engine coolant, and treat as required.
- Verify the minimum exhaust temperature and the bypass operation.
- Record the heat output, the electrical output, and the efficiencies, and compare with the design.
The maintenance keeps the recovery efficiency high and the equipment reliable. The fouled exchangers reduce the heat transfer and the back pressure increases, and the cleaning restores the performance. The maintenance schedule guide covers the intervals, and the oil cooler guide covers the related heat exchanger.
Recovery System Installation Considerations
The installation of the waste heat recovery equipment follows the engineering design and the site conditions: the heat exchangers are located with the access for the cleaning, the pipework is routed with the correct slope and the drains, and the insulation is applied to the hot surfaces. The engine exhaust connection includes the flexible section and the expansion joint, and the back pressure is verified within the engine limit. The jacket water connection is made through the isolation valves and the thermostatic control, and the engine cooling is protected at all loads.
The installation is coordinated with the engine room layout: the equipment is placed to avoid the interference with the generator maintenance, the access is maintained, and the fire and the safety requirements are met. The pipework is pressure-tested, the control system is commissioned, and the safety devices are verified. The operators are trained on the operation and the emergency shutdown. The installation record documents the equipment, the settings, and the test results. The installation guide covers the procedure, and the exhaust manifold guide covers the exhaust connection.
Performance Monitoring and Optimisation
The performance of the recovery system is monitored to verify the savings and to detect the deterioration: the electrical output, the heat output, the fuel input, the temperatures, and the flows are recorded, and the efficiencies are calculated. The recovered heat is compared with the design value, and the decline indicates the fouling, the leak, or the control problem. The monitoring is continuous or at the scheduled intervals, and the data is reviewed for the trends.
The optimisation adjusts the operation to maximise the recovery: the heat-led and the electricity-led modes are balanced, the storage and the dump are managed, and the boiler and the CHP are coordinated. The fouled exchangers are cleaned, the controls are recalibrated, and the water treatment is maintained. The optimisation reviews the load profile and the fuel price, and the operation is adjusted for the best economy. The maintenance schedule guide covers the monitoring, and the after-sales guide covers the support.
Thermal Storage and Dump Cooling
The thermal storage tank accumulates the recovered heat when the demand is lower than the generation, and it smooths the mismatch between the heat supply and the heat use. The tank is sized for the thermal capacity, typically one to several hours of the recovered heat, and it is insulated to minimise the losses. The tank is charged from the heat exchanger at the supply temperature, and the stored water is drawn for the heating and the hot water during the peaks. The storage increases the utilisation and the payback of the recovery system.
The dump cooler rejects the surplus heat when the storage is full and the demand is low: the radiator or the dump heat exchanger cools the recovered water, and the engine continues to run at the electrical demand without the overheating. The dump cooler is controlled by the temperature and the storage level, and it is rated for the full recoverable heat. The dump operation is monitored, and the excessive dumping indicates the mismatch between the generation and the demand, which is corrected by the operation planning. The radiator guide covers the cooling, and the water pump guide covers the circulation.
The storage and the dump are integrated with the control system: the pumps, the valves, and the temperature sensors are connected, and the control strategy manages the charge, the draw, and the dump. The stratification in the tank is maintained by the low-flow charging and the correct inlet and outlet positions, and the temperature sensors monitor the layers. The storage tank is inspected and cleaned at the interval, and the insulation is maintained. The correct storage and the dump design protect the engine and maximise the recovered heat. The maintenance schedule guide covers the service, and the after-sales guide covers the support.